|
P2-3. AHU and VAV Box Diagnostics > Background
Building HVAC equipment routinely fails to
satisfy performance expectations envisioned
at design. Equipment and control failures
often go unnoticed for extended periods of
time. Additionally, higher expectations are
being placed on a combination of different
and often conflicting performance measures,
such as energy efficiency, indoor air quality,
comfort, reliability, limiting peak demand
on utilities, etc. To meet these expectations,
the processes, systems, and equipment used
in both commercial and residential buildings
are becoming increasingly sophisticated.
At the same time, operations staff is stretched
thin and are often untrained in trouble-shooting
techniques. These conditions necessitate
the use of automated diagnostics to ensure
fault-free operation. The amount of data
that must be analyzed to automate fault detection
and diagnostics could overwhelm the communication
network of an HVAC system. This argues for
conducting as much analysis as possible within
local unit controllers. Modern controllers
provide a platform that is powerful and flexible
enough to perform distributed fault detection
and diagnostics (FDD) for the various building
systems.
Researchers at the National Institute for
Standards and Technology (NIST) focused on
developing FDD methods for air handling units
(AHU) and variable air volume (VAV) control
boxes. The FDD tools for AHUs and VAV boxes
were developed with distinct approaches because
of the nature of the systems. VAV boxes are
simple devices with a limited number of operation
modes and possible faults. The VAV boxes
typically have little instrumentation and
controllers with limited capability. However,
VAV boxes are very numerous in a typical
HVAC system, resulting in a large amount
of data to be monitored for faults. AHUs
are more complex and thus susceptible to
more kinds of faults. They also tend to have
more instrumentation and more capable controllers.
The FDD tools for both systems are designed
to be robust so that they can adapt to the
variety of applications typical of their
use.
NIST developed two
rule sets:
- The AHU Performance Assessment Rules (APAR)
diagnostic tool is a set of expert rules
derived from mass and energy balances that
can be used to detect common faults in air-handling
units. Control signals are used to determine
the mode of operation for the AHU. A subset
of the expert rules corresponding to that
mode of operation is then evaluated to determine
if there is a mechanical fault or a control
problem. The rules apply to single-duct,
variable-volume or constant-volume air handlers,
with hydronic heating and cooling coils and
economizers. Seven faults can be detected:
- stuck or leaking mixing box dampers
- stuck or leaking heating coil and cooling
coil valves
- temperature sensor faults
- design faults such as undersized coils
- sequencing logic errors" central plant faults that affect supply
conditions at
the AHU coils
- inappropriate operator intervention
- The VAV box Performance Assessment Control
Charts (VPACC) is a diagnostic tool that
uses statistical quality control measures
to detect faults or control problems in VAV
boxes. VPACC can be applied to most VAV box
control strategies. Fault thresholds are
determined by statistical analysis of a database
of "normal operation" data. The
rules require three commonly available sensor
measurements: (1) zone air temperature, (2)
discharge air temperature, and (3) air flow
rate. Faults due sensor drift or control
problems can be detected (see Figure 3).

Figure 3 VPACC Example
Showing How Signal
Noise is Filtered
to Show Gradual Fault
Over
Time
Back to Previous Page
|